Section 304 - Amendments and additions to NFPA related to Automatic Fire Sprinklers Systems.

UT Code § 15A-5-304 (2019) (N/A)
Copy with citation
Copy as parenthetical citation

(1) NFPA 13, Installation of Sprinkler Systems, 2016 edition. (a) NFPA 13, Chapter 8, Section 15.22, System Subdivision, is deleted and rewritten as follows: "8.15.22 System Subdivision - Floor/Zone Control Valves. Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet." (b) NFPA 13, Chapter 8, Section 8.17.1.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "8.17.1.1.1 Single Tenant Occupancies. An approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of the building, in a normally occupied location, to alert the occupants of the fire sprinkler system activation." (c) NFPA 13, Chapter 8, Section 8.17.1.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "8.17.1.1.2 Multi-Tenant Occupancies. An approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler system activation." (d) NFPA 13, Chapter 8, Section 8.17.1.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "8.17.1.1.3 Exterior Waterflow Alarm. An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."

(a) NFPA 13, Chapter 8, Section 15.22, System Subdivision, is deleted and rewritten as follows: "8.15.22 System Subdivision - Floor/Zone Control Valves. Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet."

(b) NFPA 13, Chapter 8, Section 8.17.1.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "8.17.1.1.1 Single Tenant Occupancies. An approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of the building, in a normally occupied location, to alert the occupants of the fire sprinkler system activation."

(c) NFPA 13, Chapter 8, Section 8.17.1.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "8.17.1.1.2 Multi-Tenant Occupancies. An approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler system activation."

(d) NFPA 13, Chapter 8, Section 8.17.1.1, Local Waterflow Alarms, is amended by adding a new subsection as follows: "8.17.1.1.3 Exterior Waterflow Alarm. An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."

(2) NFPA 13D, Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, 2013 edition. (a) NFPA 13D, Chapter 7, Section 7.6, Alarms, is amended by adding a new subsection as follows: "7.6.1 Exterior Waterflow Alarm. When an alarm initiating device is included, an approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ." (b) NFPA 13D, Chapter 7, Section 7.6, Alarms, is amended by adding a new subsection as follows: "7.6.2 Interior Alarm. When an alarm initiating device is included, an interior fire alarm notification appliance is also required to sound throughout the dwelling. An approved audible sprinkler flow alarm to alert the occupants of the dwelling in a normally occupied location when the flow switch is activated must be provided."

(a) NFPA 13D, Chapter 7, Section 7.6, Alarms, is amended by adding a new subsection as follows: "7.6.1 Exterior Waterflow Alarm. When an alarm initiating device is included, an approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."

(b) NFPA 13D, Chapter 7, Section 7.6, Alarms, is amended by adding a new subsection as follows: "7.6.2 Interior Alarm. When an alarm initiating device is included, an interior fire alarm notification appliance is also required to sound throughout the dwelling. An approved audible sprinkler flow alarm to alert the occupants of the dwelling in a normally occupied location when the flow switch is activated must be provided."

(3) NFPA, Standard 13R, Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, 2013 edition. (a) NFPA 13R, Chapter 6, Section 6.8, Valves, is amended by adding a new subsection as follows: "6.8.9 Floor/Zone Control Valves. Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet." (b) NFPA 13R, Chapter 6, Section 16, Alarms, is amended by adding a new subsection as follows: "6.16.1.1 Local Waterflow Alarms. An approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each residential unit/tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler system activation." (c) NFPA 13R, Chapter 6, Section 16, Alarms, is amended by adding a new subsection as follows: "6.16.1.2 Exterior Waterflow Alarm. An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."

(a) NFPA 13R, Chapter 6, Section 6.8, Valves, is amended by adding a new subsection as follows: "6.8.9 Floor/Zone Control Valves. Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet."

(b) NFPA 13R, Chapter 6, Section 16, Alarms, is amended by adding a new subsection as follows: "6.16.1.1 Local Waterflow Alarms. An approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each residential unit/tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler system activation."

(c) NFPA 13R, Chapter 6, Section 16, Alarms, is amended by adding a new subsection as follows: "6.16.1.2 Exterior Waterflow Alarm. An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."

LegalFix

Copyright ©2024 LegalFix. All rights reserved. LegalFix is not a law firm, is not licensed to practice law, and does not provide legal advice, services, or representation. The information on this website is an overview of the legal plans you can purchase—or that may be provided by your employer as an employee benefit or by your credit union or other membership group as a membership benefit.

LegalFix provides its members with easy access to affordable legal services through a network of independent law firms. LegalFix, its corporate entity, and its officers, directors, employees, agents, and contractors do not provide legal advice, services, or representation—directly or indirectly.

The articles and information on the site are not legal advice and should not be relied upon—they are for information purposes only. You should become a LegalFix member to get legal services from one of our network law firms.

You should not disclose confidential or potentially incriminating information to LegalFix—you should only communicate such information to your network law firm.

The benefits and legal services described in the LegalFix legal plans are not always available in all states or with all plans. See the legal plan Benefit Overview and the more comprehensive legal plan contract during checkout for coverage details in your state.

Use of this website, the purchase of legal plans, and access to the LegalFix networks of law firms are subject to the LegalFix Terms of Service and Privacy Policy.

We have updated our Terms of Service, Privacy Policy, and Disclosures. By continuing to browse this site, you agree to our Terms of Service, Privacy Policy, and Disclosures.
Section 304 - Amendments and additions to NFPA related to Automatic Fire Sprinklers Systems.