Section 108 - Amendments to Chapters 17 through 19 of IBC.

UT Code § 15A-3-108 (2019) (N/A)
Copy with citation
Copy as parenthetical citation

(1) A new IBC, Section 1807.1.6.4, is added as follows: "1807.1.6.4 Empirical concrete foundation design. Group R, Division 3 Occupancies three stories or less in height, and Group U Occupancies, which are constructed in accordance with Section 2308, or with other methods employing repetitive wood-frame construction or repetitive cold-formed steel structural member construction, shall be permitted to have concrete foundations constructed in accordance with Table 1807.1.6.4."

(2) A new IBC, Table 1807.1.6.4 is added as follows: "TABLE 1807.1.6.4 EMPIRICAL FOUNDATION WALLS (1,7,8) Max. HeightTop Edge SupportMin.ThicknessVertical Steel (2)Horizontal Steel (3)Steel atOpenings (4)Max. Lintel LengthMin. Lintel Length 2'(610 mm)None6"(5)2- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below2'(610 mm)2" for each foot of opening width;min. 6" 3'(914 mm)None6"#4@32"3- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below2'(610 mm)2" for each foot of opening width;min. 6" 4'(1,219 mm)None6"#4@32"4- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below3'(914 mm)2" for each foot of opening width;min. 6" 6'(1,829 mm)Floor or roof Diaphragm (6)8"#4@24"5- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below6'(1,829 mm)2" for each foot of opening width;min. 6" 8'(2,438 mm)Floor or roof Diaphragm (6)8"#4@24"6- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below6'(1,829 mm)2" for each foot of opening width;min. 6" 9'(2,743 mm)Floor or roof Diaphragm (6)8"#4@16"7- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below6'(1,829 mm)2" for each foot of opening width;min. 6" Over 9'(2,743 mm), Engineering required for each column Footnotes: (1) Based on 3,000 psi (20.6 Mpa) concrete and 60,000 psi (414 Mpa) reinforcing steel. (2) To be placed in the center of the wall, and extended from the footing to within three inches (76 mm) of the top of the wall; dowels of #4 bars to match vertical steel placement shall be provided in the footing, extending 24 inches (610 mm) into the foundation wall. (3) One bar shall be located in the top four inches (102 mm), one bar in the bottom four inches (102 mm) and the other bars equally spaced between. Such bar placement satisfies the requirements of Section 1805.9. Corner reinforcing shall be provided so as to lap 24 inches (610 mm). (4) Bars shall be placed within two inches (51 mm) of the openings and extend 24 inches (610 mm) beyond the edge of the opening; vertical bars may terminate three inches (76 mm) from the top of the concrete. (5) Dowels of #4 bar at 32 inches on center shall be provided in the footing, extending 18 inches (457 mm) into the foundation wall. (6) Diaphragm shall conform to the requirements of Section 2308. (7) Footing shall be a minimum of nine inches thick by 20 inches wide. (8) Soil backfill shall be soil classification types GW, GP, SW, or SP, per Table 1610.1. Soil shall not be submerged or saturated in groundwater."

"TABLE 1807.1.6.4

EMPIRICAL FOUNDATION WALLS (1,7,8)

Max. HeightTop Edge SupportMin.ThicknessVertical Steel (2)Horizontal Steel (3)Steel atOpenings (4)Max. Lintel LengthMin. Lintel Length

2'(610 mm)None6"(5)2- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below2'(610 mm)2" for each foot of opening width;min. 6"

3'(914 mm)None6"#4@32"3- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below2'(610 mm)2" for each foot of opening width;min. 6"

4'(1,219 mm)None6"#4@32"4- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below3'(914 mm)2" for each foot of opening width;min. 6"

6'(1,829 mm)Floor or roof Diaphragm (6)8"#4@24"5- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below6'(1,829 mm)2" for each foot of opening width;min. 6"

8'(2,438 mm)Floor or roof Diaphragm (6)8"#4@24"6- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below6'(1,829 mm)2" for each foot of opening width;min. 6"

9'(2,743 mm)Floor or roof Diaphragm (6)8"#4@16"7- #4 Bars2- #4 Bars above1- #4 Bar each side1- #4 Bar below6'(1,829 mm)2" for each foot of opening width;min. 6"

Over 9'(2,743 mm), Engineering required for each column

Footnotes:

(1) Based on 3,000 psi (20.6 Mpa) concrete and 60,000 psi (414 Mpa) reinforcing steel.

(2) To be placed in the center of the wall, and extended from the footing to within three inches (76 mm) of the top of the wall; dowels of #4 bars to match vertical steel placement shall be provided in the footing, extending 24 inches (610 mm) into the foundation wall.

(3) One bar shall be located in the top four inches (102 mm), one bar in the bottom four inches (102 mm) and the other bars equally spaced between. Such bar placement satisfies the requirements of Section 1805.9. Corner reinforcing shall be provided so as to lap 24 inches (610 mm).

(4) Bars shall be placed within two inches (51 mm) of the openings and extend 24 inches (610 mm) beyond the edge of the opening; vertical bars may terminate three inches (76 mm) from the top of the concrete.

(5) Dowels of #4 bar at 32 inches on center shall be provided in the footing, extending 18 inches (457 mm) into the foundation wall.

(6) Diaphragm shall conform to the requirements of Section 2308.

(7) Footing shall be a minimum of nine inches thick by 20 inches wide.

(8) Soil backfill shall be soil classification types GW, GP, SW, or SP, per Table 1610.1. Soil shall not be submerged or saturated in groundwater."

(3) A new IBC, Section 1905.1.9, is added as follows: "1905.1.9 ACI 318, Table 4.2.1." Modify ACI 318, Table 19.3.1.1 to read as follows: In the portion of the table designated as "Conditions", the following Exposure category and class is deleted and replaced with the following:"F0: Concrete elements not exposed to freezing and thawing cycles to include footing and foundation elements that are completely buried in soil."

LegalFix

Copyright ©2024 LegalFix. All rights reserved. LegalFix is not a law firm, is not licensed to practice law, and does not provide legal advice, services, or representation. The information on this website is an overview of the legal plans you can purchase—or that may be provided by your employer as an employee benefit or by your credit union or other membership group as a membership benefit.

LegalFix provides its members with easy access to affordable legal services through a network of independent law firms. LegalFix, its corporate entity, and its officers, directors, employees, agents, and contractors do not provide legal advice, services, or representation—directly or indirectly.

The articles and information on the site are not legal advice and should not be relied upon—they are for information purposes only. You should become a LegalFix member to get legal services from one of our network law firms.

You should not disclose confidential or potentially incriminating information to LegalFix—you should only communicate such information to your network law firm.

The benefits and legal services described in the LegalFix legal plans are not always available in all states or with all plans. See the legal plan Benefit Overview and the more comprehensive legal plan contract during checkout for coverage details in your state.

Use of this website, the purchase of legal plans, and access to the LegalFix networks of law firms are subject to the LegalFix Terms of Service and Privacy Policy.

We have updated our Terms of Service, Privacy Policy, and Disclosures. By continuing to browse this site, you agree to our Terms of Service, Privacy Policy, and Disclosures.
Section 108 - Amendments to Chapters 17 through 19 of IBC.