76-3504. Radon resistant new construction; minimum standards.

Except as provided in section 76-3505, new construction built after September 1, 2019, in the State of Nebraska that is intended to be regularly occupied by people shall be built using radon resistant new construction. Such construction shall meet the following minimum standards:

(1) Sumps:

(a) A sump pit open to soil or serving as the termination point for subslab or exterior drain tile loops shall be covered with a gasketed or otherwise sealed lid;

(b) A sump used as the suction point in a subslab depressurization system shall have a lid designed to accommodate the vent pipe; and

(c) A sump used as a floor drain shall have a lid equipped with a trapped inlet;

(2) A passive subslab depressurization system shall be installed during construction in basement or slab-on-grade buildings, including the following components:

(a) Vent pipe:

(i)(A) A minimum three-inch diameter acrylonitrile butadiene styrene (ABS), polyvinyl chloride (PVC), or equivalent gas-tight pipe shall be embedded vertically into the subslab permeable material before the slab is cast. A "T" fitting or equivalent method shall be used to ensure that the pipe opening remains within the subslab permeable material; or

(B) A minimum three-inch diameter ABS, PVC, or equivalent gas-tight pipe shall be inserted directly into an interior perimeter drain tile loop or through a sealed sump cover where the sump is exposed to the subslab or connected to it through a drainage system;

(ii) The pipe shall be extended up through the building floors and terminate at least twelve inches above the surface of the roof in a location at least ten feet away from any window or other opening into the conditioned spaces of the building that is less than two feet below the exhaust point and ten feet from any window or other opening in adjoining or adjacent buildings; and

(iii) In buildings where interior footings or other barriers separate the subslab gas-permeable material, each area shall be fitted with an individual vent pipe. Vent pipes shall connect to a single vent that terminates above the roof or each individual vent pipe shall terminate separately above the roof. All exposed and visible interior radon vent pipes shall be identified with at least one label on each floor and in accessible attics. Such label shall read: Radon Reduction System; and

(3) Power source: In order to provide for future installation of an active radon mitigation system, an electrical circuit terminated in an approved box shall be installed during construction in the attic or other anticipated location of vent pipe fans.

Source

LegalFix

Copyright ©2024 LegalFix. All rights reserved. LegalFix is not a law firm, is not licensed to practice law, and does not provide legal advice, services, or representation. The information on this website is an overview of the legal plans you can purchase—or that may be provided by your employer as an employee benefit or by your credit union or other membership group as a membership benefit.

LegalFix provides its members with easy access to affordable legal services through a network of independent law firms. LegalFix, its corporate entity, and its officers, directors, employees, agents, and contractors do not provide legal advice, services, or representation—directly or indirectly.

The articles and information on the site are not legal advice and should not be relied upon—they are for information purposes only. You should become a LegalFix member to get legal services from one of our network law firms.

You should not disclose confidential or potentially incriminating information to LegalFix—you should only communicate such information to your network law firm.

The benefits and legal services described in the LegalFix legal plans are not always available in all states or with all plans. See the legal plan Benefit Overview and the more comprehensive legal plan contract during checkout for coverage details in your state.

Use of this website, the purchase of legal plans, and access to the LegalFix networks of law firms are subject to the LegalFix Terms of Service and Privacy Policy.

We have updated our Terms of Service, Privacy Policy, and Disclosures. By continuing to browse this site, you agree to our Terms of Service, Privacy Policy, and Disclosures.
76-3504 Radon resistant new construction; minimum standards.