Section 25-9-274 - Electrical equipment installations and inspections; grounding and insulation of electrical equipment; trailing cables.

AL Code § 25-9-274 (2019) (N/A)
Copy with citation
Copy as parenthetical citation

(a) Installations and inspections. All electrical equipment installations shall be approved and all electrical inspections made by a qualified person.

(b) Grounding.

(1) Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings, and other metallic enclosures, such grounding wires will be approved if:

a. The cross-sectional area (size) of the grounding wire is at least one-half the cross-sectional area (size) of the power conductor where the power conductor used is No. 6 A.W.G. or larger.

b. Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area (size) of the grounding wire is equal to the cross-sectional area (size) of the power conductor.

(2) The protective grounding of electrical circuits and equipment to water pipe systems, when available, is desired as such grounding offers the most effective protection to life and property. Gas or air pipelines shall not be used for grounding circuits. Metal well casings, metal drain pipes, and similar buried metal structures of considerable extent may be used in lieu of extended buried water piping systems.

(3) The ground connection to metallic piping systems shall be made by means of a suitable connection firmly attached to the pipe after all rust and scale have been removed, or by means of a brass plug which has been tightly screwed into a pipe fitting or, where the pipe is of sufficient thickness, screwed into a hole in the pipe itself or by other equivalent means. The grounding conductor shall be attached to the clamp or to the plug by means of solder or a suitable solderless connector.

(4) If conduit, couplings, or fittings having protective coatings of nonconducting material, such as enamel, are used, such coating shall be thoroughly removed from couplings, conduits, and such surfaces of fittings where the conduit or ground connection is secured in order to obtain a good connection.

(5) Artificial grounds should be located where practicable below permanent moisture level, or, failing in this, a suitable means of grounding shall be used.

(6) Where copper ground plates are used, they should be at least six hundredths of an inch thick. When driven pipes are used, they should be of galvanized iron and not smaller than three fourths of an inch internal diameter, and when cast iron plates are used they should be at least twenty-five hundredths of an inch thick.

(c) Insulation.

(1) All fixed electric light and power lines, regardless of voltage, shall be properly supported on standard insulators.

(2) Drop cord extension light lines shall be flexible with heavy rubber insulation, equipped with a heavy wire light globe shield, hook, and heavy rubber handle.

(d) Trailing cables.

(1) Where employees are required to handle energized high voltage trailing cables, they shall be required to use cable tongs and wear rubber gloves. Where surroundings are wet, such employees shall also be required to wear rubber boots.

(2) Damage to the insulation of trailing cables shall be promptly reported and repairs made. Splicing shall be done only by a competent electrician or person competent to splice cables, and splices shall be made moisture-proof. Where it is necessary for mechanical equipment to cross a cable, safe cable bridges shall be provided and used. Where armored cables or conduit are used, the armor or metal conduit shall be electrically continuous, and, when necessary to splice armored cable, the broken section of the armor shall be bonded to insure electrical continuity.

LegalFix

Copyright ©2024 LegalFix. All rights reserved. LegalFix is not a law firm, is not licensed to practice law, and does not provide legal advice, services, or representation. The information on this website is an overview of the legal plans you can purchase—or that may be provided by your employer as an employee benefit or by your credit union or other membership group as a membership benefit.

LegalFix provides its members with easy access to affordable legal services through a network of independent law firms. LegalFix, its corporate entity, and its officers, directors, employees, agents, and contractors do not provide legal advice, services, or representation—directly or indirectly.

The articles and information on the site are not legal advice and should not be relied upon—they are for information purposes only. You should become a LegalFix member to get legal services from one of our network law firms.

You should not disclose confidential or potentially incriminating information to LegalFix—you should only communicate such information to your network law firm.

The benefits and legal services described in the LegalFix legal plans are not always available in all states or with all plans. See the legal plan Benefit Overview and the more comprehensive legal plan contract during checkout for coverage details in your state.

Use of this website, the purchase of legal plans, and access to the LegalFix networks of law firms are subject to the LegalFix Terms of Service and Privacy Policy.

We have updated our Terms of Service, Privacy Policy, and Disclosures. By continuing to browse this site, you agree to our Terms of Service, Privacy Policy, and Disclosures.
Section 25-9-274 - Electrical equipment installations and inspections; grounding and insulation of electrical equipment; trailing cables.