§ 420.66 - Separation distance requirements for storage of hydrogen peroxide, hydrazine, and liquid hydrogen and any incompatible energetic liquids stored within an intraline distance.

Copy with citation
Copy as parenthetical citation

Separation of energetic liquids and determination of distances. A launch site operator must separate each explosive hazard facility from each other explosive hazard facility, each public area, and each public traffic route in accordance with the minimum separation distance determined under this section for each explosive hazard facility storing:

Hydrogen peroxide in concentrations of greater than 91 percent;

Hydrazine;

Liquid hydrogen; or

Any energetic liquid that is:

Incompatible with any of the energetic liquids of paragraph (a)(1) through (3) of this section; and

Stored within an intraline distance of any of them.

Quantity. For each explosive hazard facility, a launch site operator must determine the total quantity of all energetic liquids in paragraph (a)(1) through (4) of this section as follows:

The quantity of energetic liquid in a tank, drum, cylinder, or other container is the net weight in pounds of the energetic liquid in the container. The determination of quantity must include any energetic liquid in associated piping to any point where positive means exist for:

Interrupting the flow through the pipe, or

Interrupting a reaction in the pipe in the event of a mishap.

A launch site operator must convert the quantity of each energetic liquid from gallons to pounds using the conversion factors provided in table E-6 of appendix E of this part and the following equation:

Where two or more containers of compatible energetic liquids are stored in the same explosive hazard facility, the total quantity of energetic liquids is the total quantity of energetic liquids in all containers, unless:

The containers are each separated from each other by the distance required by paragraph (c) of this section; or

The containers are subdivided by intervening barriers that prevent mixing, such as diking.

Where two or more containers of incompatible energetic liquids are stored within an intraline distance of each other, paragraph (d) of this section applies.

Determination of separation distances for compatible energetic liquids. A launch site operator must determine separation distances for compatible energetic liquids as follows:

To determine each intraline, public area, and public traffic route distance, a launch site operator must use the following tables in appendix E of this part:

Table E-7 for hydrogen peroxide in concentrations of greater than 91 percent; and

Table E-8 for hydrazine and liquid hydrogen.

For liquid hydrogen and hydrazine, a launch site operator must use the “intraline distance to compatible energetic liquids” for the energetic liquid that requires the greater distance under table E-8 of appendix E of this part as the minimum separation distance between compatible energetic liquids.

Determination of separation distances for incompatible energetic liquids. If incompatible energetic liquids are stored within an intraline distance of each other, a launch site operator must determine the explosive equivalent in pounds of the combined liquids as provided by paragraph (d)(2) of this section unless intervening barriers prevent mixing.

If intervening barriers prevent mixing, a launch site operator must separate the incompatible energetic liquids by no less than the intraline distance that tables E-7 and E-8 of appendix E of this part apply to compatible energetic liquids using the quantity or energetic liquid requiring the greater separation distance.

A launch site operator must use the formulas provided in table E-5 of appendix E of this part, to determine the explosive equivalent in pounds of the combined incompatible energetic liquids. A launch site operator must then use the explosive equivalent in pounds requiring the greatest separation distance to determine the minimum separation distance between each explosive hazard facility and all other explosive hazard facilities and each public area and public traffic route as required by tables E-1, E-2 and E-3 of appendix E of this part.

LegalFix

Copyright ©2024 LegalFix. All rights reserved. LegalFix is not a law firm, is not licensed to practice law, and does not provide legal advice, services, or representation. The information on this website is an overview of the legal plans you can purchase—or that may be provided by your employer as an employee benefit or by your credit union or other membership group as a membership benefit.

LegalFix provides its members with easy access to affordable legal services through a network of independent law firms. LegalFix, its corporate entity, and its officers, directors, employees, agents, and contractors do not provide legal advice, services, or representation—directly or indirectly.

The articles and information on the site are not legal advice and should not be relied upon—they are for information purposes only. You should become a LegalFix member to get legal services from one of our network law firms.

You should not disclose confidential or potentially incriminating information to LegalFix—you should only communicate such information to your network law firm.

The benefits and legal services described in the LegalFix legal plans are not always available in all states or with all plans. See the legal plan Benefit Overview and the more comprehensive legal plan contract during checkout for coverage details in your state.

Use of this website, the purchase of legal plans, and access to the LegalFix networks of law firms are subject to the LegalFix Terms of Service and Privacy Policy.

We have updated our Terms of Service, Privacy Policy, and Disclosures. By continuing to browse this site, you agree to our Terms of Service, Privacy Policy, and Disclosures.
§ 420.66 - Separation distance requirements for storage of hydrogen peroxide, hydrazine, and liquid hydrogen and any incompatible energetic liquids stored within an intraline distance.